  "name": "AFDD (Prospective)",
  "climate_zone": "all",
  "bldg_type": "all commercial",
  "structure_type": "all",
  "end_use": ["heating", "cooling", "ventilation"],
  "fuel_type": "all",
  "technology": "all",
  "market_entry_year": 2020,
  "market_entry_year_source": {
    "notes": "Based on BTO target for short-term market introduction (3-5 years)",
    "source_data": null},
  "market_exit_year": null,
  "market_exit_year_source": null,
  "energy_efficiency": 0.20,
  "energy_efficiency_units": "relative savings (constant)",
  "energy_efficiency_source": {
    "note": "Based on typical relative HVAC savings range of 15%-30%",
    "source_data": [{
      "title": "Energy Impact of Commercial Building Controls and Performance Diagnostics: Market Characterization, Energy Impact of Building Faults and Energy Savings Potential",
      "author": "Roth et al.",
        "organization": "TIAX, LLC",
        "year": 2005,
      "pages": null,
      "URL": "http://s3.amazonaws.com/zanran_storage/www.tiaxllc.com/ContentPages/42428345.pdf"},
      {
      "title": "Advanced Automated HVAC Fault Detection and Diagnostics Commercialization Program",
      "author": "Frey D. and Smith V.",
        "organization": "California Energy Commission",
        "year": 2008,
      "pages": null,
      "URL": "http://www.energy.ca.gov/2013publications/CEC-500-2013-054/CEC-500-2013-054.pdf"},
      {
      "title": "Energy Savings Potential and RD&D Opportunities for Commercial Building HVAC Systems",
      "author": "Goetzler et al.",
        "organization": "Navigant Consulting",
        "year": 2011,
      "pages": null,
      "URL": "http://apps1.eere.energy.gov/buildings/publications/pdfs/corporate/savings_potential_comm_hvac.pdf"},
      {
      "title": "Review of automated fault detection and diagnostic tools in air handling units",
      "author": "Bruton et al.",
        "organization": "University College Cork",
        "year": 2011,
      "pages": [335, 335],
      "URL": "http://link.springer.com/article/10.1007/s12053-013-9238-2"},
      {
      "title": "A rule-based fault detection method for air handling units",
      "author": "Schein et al.",
        "organization": "National Institute of Standards Technology (NIST)",
        "year": 2006,
      "pages": [1485, 1492],
      "URL": "http://fire.nist.gov/bfrlpubs/build07/PDF/b07023.pdf"}]},
  "installed_cost": 0.10,
  "cost_units": "2016$/ft^2 floor",
  "installed_cost_source": {
    "notes": "BTO Prioritization Tool analysis assuming 20% HVAC energy savings and 1 year payback threshold",
    "source_data": {
      "title": "A Tool to Prioritize Energy Efficiency Investments",
      "author": "Farese et al.",
      "organization": "National Renewable Energy Laboratory",
      "year": 2012,
      "pages": null,
      "URL": "http://www.nrel.gov/docs/fy12osti/54799.pdf"}},
  "product_lifetime": 15,
  "product_lifetime_units": "years",
  "product_lifetime_source": {
    "notes": "Based on lifetime for commercial rooftop AC in 'rsclass.txt' file",
    "source_data": {
      "title": "Commercial Demand Module of the National Energy Modeling System: Model Documentation 2014", 
      "author": "U.S. Energy Information Administration (EIA)",
      "organization":  "U.S. Energy Information Administration (EIA)",
      "year": 2014,
      "pages": null,
      "URL": "https://www.eia.gov/forecasts/aeo/nems/documentation/commercial/pdf/m066(2014).pdf"}},
  "measure_type": "add-on",
  "fuel_switch_to": null,
  "market_scaling_fractions": {
    "new": 1,
    "existing": 0.43},
  "market_scaling_fractions_source": {
    "new": "Assumes that all new commercial buildings are constructed with BAS",
    "existing": {
      "title": "CBECS 2012 - Table B1. Summary table: total and means of floorspace, number of workers, and hours of operation, 2012",
      "author": "U.S. Energy Information Administration (EIA)",
      "organization": "U.S. Energy Information Administration (EIA)",
      "year": "2012",
      "URL": "http://www.eia.gov/consumption/commercial/data/2012/bc/cfm/b1.cfm",
      "fraction_derivation": "37051 ft^2 floor of commercial buildings with BAS / 87093 ft^2 floor total commercial buildings"}},
  "_description": "Ongoing, automated commissioning that compares top-level or sub-metered information about building energy use to an appropriate baseline to identify and diagnose operational faults",
  "_notes": null,
  "_added_by": {
    "name": "Jared Langevin",
    "organization": "Lawrence Berkeley National Lab",
    "email": "jared.langevin@lbl.gov",
    "timestamp": "2017-01-04 15:53:21 EST"
  },
  "_updated_by": {
    "name": null,
    "organization": null,
    "email": null,
    "timestamp": null
  }
}